IGS-NT Installation Guide
125
SG COM
SG OUT
Vout
36
8 ( 0 to 10 VDC
)
MTU MDEC
2000, 4000
Pay attention to the connector and jumper orientation.
Sync/Load ctrl:
Speed gov bias = 4,90 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0V
SpeedGovHiLim = 10V
DEUTZ
SG COM
SG OUT
Vout
23
GND
24
(0, 5 to 4,5
VDC
)
DEUTZ
BF6M
21
17
Opened for
0% Droop
Plug F
Pay attention to the connector and jumper orientation.
Sync/Load ctrl:
Speed gov bias = 2,50 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0,5V
SpeedGovHiLim = 4,5V
PERKINS
SG COM
SG OUT
Vout
19
PERKINS
4016 E61 TRS
18
Pay attention to the connector and jumper orientation.
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 2,5V
SpeedGovHiLim = 7,5V
SG COM
SG OUT
Vout
PERKINS
2300, 2800
20
24
12
2
Pay attention to the connector and jumper orientation.
Above mentioned pin numbers refer to the Customer Interface
Connector. The J1 connector on ECM has the following
numbering:
20 = J1/3; 24 = J1/17
Sync/Load ctrl:
Speed gov bias = 2,50 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0,5V
SpeedGovHiLim = 4,5V
VBREF GND
RPS INPUT
PERKINS
1300 EDi
SG COM
SG OUT
VoutR
Sync/Load ctrl:
Speed gov bias = 2,5 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0,8V
SpeedGovHiLim = 4,5V
TOHO

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals