Low Power Outdoor (LPOD) Amplifier/Block Up Converter (BUC)
Revision 15
Serial Interface Operation 5–27 MN-LPOD
Parameter
Type
(* indicates
End-of-Life)
Instruction Code and
Arguments
for Command
or Query
Description of Arguments
(Note that all arguments are ASCII numeric codes from 48 to 57)
(see Description of
Command Query
Response to
Command
Response
to Query
Sets or returns the alarm mask conditions in the form abcde where:
a=Low Forward RF Power
b=External Reference Lock detect
c=Fan Speed
d=LNB Current Detect
e=LNB 22V Power Supply
TYPICAL FOR EACH PARAMETER: 0=Fault, 1=Alarm, 2=Masked
NOTES:
1) Default value: 22111
2) If the value is set to ‘Fault’ (MSK=0) for a parameter, then the fault condition
will be logged as a fault if specified hardware conditions are not met.
3) If the mask value is set to ‘Alarm’ (MSK=1), then the fault condition will only
log as an alarm.
4) If the mask value is set to ‘Masked’ (MSK=2), then the fault condition will
not be reported to the user.
COMMAND EXAMPLE: <0001/MSK=22111{CR}
MSK?
MSK*
e
Sets or returns the unit muting in the form x, where:
0=Disable (Not Muted)
1=Enable (Muted) (DEFAULT)
2=Unit muted due to HW mute signal (SEE NOTE)
NOTE: This value is only shown in the response to a query, and cannot be issued
as a command. When MUT=2 this means that one of the “hardware” mute
conditions is present. Additionally, certain faults can generate a hardware mute,
e.g., BUC Lock Detect. If MUT=2, you must check the active faults and the status
of the auxiliary mute.
COMMAND EXAMPLE: <0001/MUT=1{CR}
MUT?
MUT*
Unread Stored
Events
Unit returns the Number of Unread stored Events in the form xxx.
EXAMPLE: <0001/NUE?{CR}