108
6.19 Modbus Slave (Hexadecimal Address)
HM Series Connection Manual
6.19. Modbus Slave (Hexadecimal Address)
6.19.1. Register Type & Range: (Addresses of
Hexadecimal Values)
Register Type
Code Format
Numbering Range of Address
Data Length
Holding_REG
4Xnnnn
nnnn=0~FFFF
Word
Input_REG
3Xnnnn
nnnn=0~FFFF
Word
Holding_REG
4Lnnnn
nnnn=0~FFFE
DWord
Input_REG
3Lnnnn
nnnn=0~FFFE
DWord
6.19.2. Contact Type & Range:(Addresses of
Hexadecimal Values)
Contact Type
Code Format
Numbering Range of Address
Block
Coil_STATUS
0Xnnnn
nnnn=0~FFFF
Input_STATUS
1Xnnnn
nnnn=0~FFFF
6.19.3. Settings of Communication Parameters:
(According to Linked Device)
Parameters
Default Value
Setting Range
Device Address
1
1 ~ 247
Communication Mode
RS232
RS232 / RS485 / RS422
Baud Rate
9600 bps
2400 bps ~ 115200 bps
Data Length
8 bits
7 bits / 8 bits ( RTU can only be 8 bits )
Parity Check
None
None / Odd / Even
Stop Bit
1 bit
1 bit / 2 bits
Command Delay Time
0
0 ~ 1000 ms
HMI Address
Null