53
HM Series Connection Manual
6.7.2. Contact Type & Range:(Value Addresses of Octal
Number System)
Contact Type
Code Format
Numbering Range of Address
Block
Input relay
Xn
n = 0~1777
Output relay
Yn
n = 0~1777
Internal relay
Cn
n = 0~3777
Stages
Sn
n = 0~1777
Timer relay
Tn
n = 0~377
Counter relay
CTn
n = 0~377
Special relay
SPn
n = 0~777
Remote Input
GXn
n = 0~377
Remote Output
GYn
n = 0~377
6.7.3. Settings of Communication Parameters:
(According to Linked Device)
Parameters
Default Value
Setting Range
Device Address
1
Communication Mode
RS232
Baud Rate
9600 bps
Data Length
8 bits
Parity Check
Odd
Stop Bit
1 bit
Command Delay Time
0
0 ~ 1000 ms
HMI Address
Null