19Operating the control software
5.1.1 Operating status indication
The following operation status indications may appear during operation:
Operating status indication Description
The Condair EL is in standby mode (no demand present).
The Condair EL is performing a cylinder ushing.
There has been no demand for humidity for an extended period of time. The humidier idle
drain function has drained the steam cylinder. The steam cylinder will automatically be relled
when humidication is required.
The Condair EL is producing, or is trying to produce, steam.
The Condair EL is in standby mode and the keep warm function is activated.
The Condair EL is disabled by Building Automation System or by the external enable contact
(if enabled).
The external safety loop is open and has stopped the Condair EL. Check On/Off monitoring
devices connected to safety loop.
The Condair EL is stopped due to a malfunction which prevents further operation. Additionally
"Warning" or "Fault" is displayed in the maintenance and malfunction eld.
5.1.2 Maintenance and malfunction indications
The following maintenance and malfunction indications may appear during operation:
Maintenance and
malfunction indication
Description
No malfunction present. By pressing on the indication eld the service menu can be accessed.
This message appears if the control software has detected that the steam cylinder is spent. If
the steam cylinder is not replaced or serviced, and the "Cylinder spent" message is not reset
within 7 days, a corresponding fault message appears.
Replace the steam cylinder or service the reusable cylinder, then reset the "Cylinder spent"
message via the "Service" submenu.
A malfunction with status "Warning" is active. In addition, the humidier's yellow warning LED
light will be active. Depending upon the malfunction, the Condair EL is either be stopped or
stays operable for a certain period of time.
A malfunction with status "Fault" is active. In addition, the humidier's red error LED light will
be active. The Condair EL is stopped.