63Maintenance
Unit component What to clean and how to clean
Drain cup
• Use a soft bristled brush (do not use a wire brush) to
remove any limescale from the drain cup and its con-
nectors.
If the drain cup is heavily calcied, place it in an 8%
formic acid solution (observe safety notes in chapter
6.5), until the limescale comes off.
• Rinse the drain cup with hot tap water.
Interior of the unit
(water side only)
Wipe the interior of the unit with a damp cloth without using
any cleaning agent.
CAUTION! Take care that the electrical connections and
the electronic components remain dry.
6.5 Notes on cleaning agents
Only use cleaning agents stated in the table above. The use of disinfectants is only permitted if they
do not leave any toxic residues. In any case the parts must be thoroughly rinsed with hot tap water after
cleaning.
Do not use soap to clean the parts since residual soap can cause foaming which will affect proper
operation of the humidier.
WARNING!
Formic acid is indeed harmless to the skin, but it attacks the mucous membranes. Therefore prevent
your eyes and respiratory tracts from getting in touch with the acid and its vapours (wear goggles and
work in a well ventilated room or outside).
CAUTION!
Donotuseanysolvents,aromatizedorhalogenizedhydrocarbonsorotheraggressivesub-
stances as they may cause damage to the components of the unit.
It is mandatory to observe and comply with the information and instructions regarding cleaning agents.
Observe in particular: all information relating to the protection of personnel, environmental protection
and restrictions regarding usage.