20 Notes for the planning engineer
4 Notes for the planning engineer
4.1 Selecting the unit version
To select the unit version the following planning steps are required:
1. Determinating the required maximum steam capacity according chapter 4.1.1
2. Selecting the unit version from the table in chapter 4.1.2
4.1.1 Determinatingthemaximumrequiredsteamcapacity
The maximum required steam capacity for a steam bath is determined according to the table below:
Cabin size Requiredsteamcapacity
Plastic cabin brick lined cabin
4 m
3
4 kg/h 8 kg/h
8 m
3
8 kg/h 12 kg/h
12 m
3
10 kg/h 15 kg/h
16 m
3
12 kg/h 18 kg/h
20 m
3
13 kg/h 21 kg/h
24 m
3
15 kg/h 24 kg/h
28 m
3
17 kg/h 26 kg/h
32 m
3
18 kg/h 29 kg/h
36 m
3
20 kg/h 31 kg/h
40 m
3
21 kg/h 34 kg/h
44 m
3
23 kg/h 36 kg/h
48 m
3
24 kg/h 38 kg/h
52 m
3
26 kg/h 41 kg/h
56 m
3
27 kg/h 43 kg/h
60 m
3
29 kg/h 45 kg/h
Important notes:
The steam capacity determined based on the table above does not consider any steam loss (e.g.
due to condensation in the steam hoses and the steam distributors), any heat loss of the unit as well
as any absorption or release of humidity of materials located in the room being humidi ed.
In addition, the calculated steam capacity does not consider any losses caused by the draining rate
depending on the water quality as well as any losses occur if the steam generator is operated on a
mains circuit with a ground fault circuit interrupter.
The total amount of losses depends on the entire system and must be taken into consideration when
determining the required steam capacity. If you have any questions regarding the calculation of the
steam capacity please contact your Condair supplier.