67Maintenance
7.4 Notes on cleaning the unit components
Unit component What to clean and how to clean
Water hoses
Loosen any limescale in the hoses by carefully twisting
and exing the hoses, then suh out the hoses thoroughly
with hot water.
Inlet valve
strainer insert
Carefully remove any limescale inside the inlet valve
and on the strainer using a brush (do not use a wire
brush).
Wash inlet valve and strainer insert with a lukewarm
soap solution, then rinse well with tap water.
Let the inlet valve dry before reinstallation!
Drain valve
valve housing
valve stem
Carefully remove any limscale from the valve housing,
the bores and the valve seat on the valve stem using a
brush (do not use a wire brush).
Wash the valve housing and the valve stem with a
lukewarm soap solution, rinse the parts well with tap
water and let them dry.
Water cup
Carefully remove any limscale from the water cup and
its connectors using a brush (do not use a wire brush).
If the water cup is heavily calcied, place it in an 8%
formic acid solution (observe safety notes in chapter
7.5), until the limescale comes off.
Wash the water cup with a lukewarm soap solution and
rinse well with tap water.