43Mounting and installation work
5.6.4 Installation work external connections
5.6.4.1 Connecting the external safety chain
Condair Sigma 4 kg/h
SAFETY
X6
J
12
SC1
24 VDC
SC2
SC1SC2
K
B1
max.
T /
Control compartment
Do not apply external
voltage via K!
The potential-free contacts of external moni t or ing de-
vices (e.g.safety humidistat "B1") are connected in series
(safety chain "K") to the terminals "SC1" and "SC2" of
the terminal block "X6" on the driver board in accord-
ance with the wiring diagram.
The connecting cable must be led through a cable gland
into the control compartment.
Note: If, for whatever reason, no external monitoring de-
vices are connected, a jumper wire "J" must be installed
on the contacts "SC1" and "SC2" of the terminal block.
CAUTION! Do not apply any external voltage to
contacts "SC1" and "SC2" via the contacts of the
external monitoring devices.
Condair Sigma 5-65 kg/h
X3
MAIN SUPPLY
L1 N SC1SC2
B1
K
J
max.
T /
Control compartment
Do not apply
external voltage
via K!
DANGER:
240 V
The potential-free contacts (max. contact load 250V/5A)
of external moni t or ing devices (e.g.safety humidistat
"B1") are connected in series (safety chain "K") to the
terminals "SC1" and "SC2" of the terminal block "X3" on
the driver board in accordance with the wiring diagram.
The connecting cable must be led through a cable gland
into the control compartment.
Note: If, for whatever reason, no external monitoring de-
vices are connected, a jumper wire "J" must be installed
on the contacts "SC1" and "SC2" of the terminal block.
CAUTION! Do not apply any external voltage to
contacts "SC1" and "SC2" via the contacts of the
external monitoring devices.
DANGER! There is mains voltage (up to 240 V) at the
connection terminal "X3". Therefore, disconnect the
steam generator from the power supply before you start
the connection work.