59Maintenance
7.2 Maintenance list
To maintain operational safety the Condair Sigma steam generator must be maintained at regular inter-
vals. This is differentiated between the first maintenance after approx. 500 operating hours (I), steam
cylinder replacement after the yellow LED lights (II) and annual maintenance (III).
Below you will nd a summary of the work to be carried out for each of the three maintenance stages.
Components Interval Work to be done
I II III
Replacement steam cylinder X Remove and replace.
Drain valve X Remove, disassemble and clean, replace if necessary.
Steam cylinder receptacle X Inspect, clean if necessary.
Inlet valve X Remove and clean lter insert, replace if necessary.
Drain cup X Remove and clean if necessary
Drain pipe and siphon X Inspect, clean if necessary (decalcify and rinse out).
Steam installation X X Inspect steam and condensate hoses for cracks and to
see that they are correctly attached, replace faulty hoses.
Water installation X X Inspect water hoses in the unit for cracks and to see
that they are correctly attached, replace faulty hoses
Check supply pipe is tight, make tight if necessary.
Clean water lter, if available.
Electrical installation X X Check all cables in the unit are rmly positioned and
examine status of insulation.

Table of Contents