Parameter
structure
Keypad and
display
Parameter x.00
Parameter
description format
Advanced parameter
descriptions
Serial comms
protocol
Performance
Menu 5
Mentor MP Advanced User Guide 89
Issue Number: 4 www.controltechniques.com
Define the time in seconds, after the field goes into economy mode after
1. The drive becomes inactive
or
2. At power up
or
3. After the drive has been reset.
The time out is selected by Pr 5.65.
Sets the reduced field current level used when the field economy function is used.
Figure 5-17 Time diagram when economy timeout selected (Pr 5.65 = 1)
5.66
Field economy timeout time
Coding
BitSP FI DETEVMDPNDRANCNVPTUSRWBUPS
111
Range
0 to 255s
Default
30 s
Update rate Background read
5.67
Field economy level
Coding
BitSP FI DETEVMDPNDRANCNVPTUSRWBUPS
1 111
Range
0 to 120.0 %
Default
25 %
Update rate Background read
Power on
Field current
Sequencer run
Disable
Drive active
Speed
Stop command
Field economy
Active
Reset
Reset action
100ms100ms
Pr
5.66
Pr
6.54
Pr
5.66
Pr
5.66
Pr
5.66
Pr
6.54