EasyManuals Logo

Control Techniques UD70 User Manual

Control Techniques UD70
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #144 background imageLoading...
Page #144 background image
UD70
Issue code: 70nu2
10-2 Parameters
Function Parameter Min Value Max Value Default
RS485 scale factor #17.10 0.000 4.000 1.000
Defines the scaling factor used in mode 3 serial communications.
Clock section timebase (ms) #17.11 5 200 10
Defines the clock period time in milliseconds for executing the CLOCK task of a DPL
program. Range: 5 to 200ms
Position controller setup #17.12 0 2 0
Defines the clock period time in milliseconds for executing the CLOCK task of a DPL
program. REINIT command does not read this parameter.
Auto-run mode #17.13 0 1 1
When set at 1, #17.13 enables a DPL program to be automatically started when the
UD70 is reset or AC power is applied. When #17.13 is set at 0, a command must be
issued from the UD70 Toolkit software before the DPL program will start.
Note: Default is 0 on Unidrives with V2.xx.xx software.
Global run-time trip
enable
#17.14 0 1 0
When #17.14 is set at 1, any run-time trips that occur will cause the Drive to trip, with
the exception of RS485-port trips (see #17.15).
When #17.14 is set at 0, only fatal run-time trips will cause the Drive to trip.
RS485 trip mode #17.15 0 1 0
If an RS485-port trip occurs (such as loss of communications in mode 3, 4 or 10) and
#17.14 and #17.15 are set at 1, the Drive will trip. If #17.14 or #17.15 is set at 0, the
Drive will not trip, but all tasks will stop.

Table of Contents

Other manuals for Control Techniques UD70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Control Techniques UD70 and is the answer not in the manual?

Control Techniques UD70 Specifications

General IconGeneral
BrandControl Techniques
ModelUD70
CategoryControl Unit
LanguageEnglish

Related product manuals