2-3
Copyright 2017 Cummins Inc.
FRONT PANEL
Figure 2-1 shows the features of the front panel.
AC Voltmeter: Dual scale instrument indicates AC
voltage. Measurement scale in use is shown on
scale indicator lamp.
AC Ammeter: Indicates current output in percent of
maximum rated current. (Percent current is based
on .8 PF.)
Kilowatt Meter: Indicates 3-phase AC power out-
put as percent of rated load.
Frequency Meter: Indicates alternator output fre-
quency in hertz.
Upper and Lower Scale Indicator Lamps: Indi-
cate AC voltmeter scale.
Digital Display: This two-line, 16-character per line
alphanumeric display is used in the menu-driven
operating system, in conjunction with the display
menu selection switches and the Menu switch. Re-
fer to the menu trees later in this section. The dis-
play is also used to show warning and shutdown
messages.
Display Menu Selection Switches: Four momen-
tary switches—two on each side of the digital dis-
play window—are used to step through the various
menu options and to adjust generator set parame-
ters. The green arrow adjacent to the switch is lit
when the switch can be used (switch is “active”).
Menu Switch: Press this switch to return the digital
display to the MAIN MENU. Refer to the menu trees
later in this section.
Reset Switch: Press this switch to reset warning
and shutdown messages after the condition has
been corrected. To reset a shutdown message with
the Reset switch, the Run/Off/Auto switch must be
in the Off position.
With the Run/Off/Auto switch in the Auto mode,
shutdown faults can be reset by removing the re-
mote start input and then cycling the remote reset
input.
Self Test Switch: Press and hold this switch to light
all front panel LEDs and cycle through all shutdown
and warning messages.
In the Standby (sleep) mode, with the generator set
not running, the control’s operating software is inac-
tive and the LEDs and displays on front panel are all
off.
To activate and view the menu displays without
starting the generator set, press and hold the Self
Test switch until the front panel LEDs light. The
PCC will initialize the operating software and permit
operation of the menu display panel. If no menu
selections are made, a software timer will shut
down the power after 30 seconds.
Panel Lights Switch: Press this switch to turn con-
trol panel illumination on and off. The illumination
will shut off after about eight minutes.
Phase Selector Switch and Indicators: Press this
momentary switch to select phases of alternator
output to be measured by the analog AC voltmeter
and ammeter. LEDs indicate the selected phase.
Run/Off/Auto Switch: This switch starts and stops
the set locally, or enables start/stop control of the
engine from a remote location. (Ground to start.)
Emergency Stop Button: Push the switch in for
emergency shutdown of the engine.
Remote Reset switch will not reset emergency stop.
Can only be reset at the PCC front panel.
To reset:
1. Turn the switch clockwise and allow it to pop
out.
2. Move the Run/Off/Auto switch to Off.
3. Press the front panel Reset switch.
4. Select Run or Auto, as required.
Non-Automatic Status Indicator: This red lamp
flashes continuously when the Run/Off/Auto switch
is not in the Auto position.
Warning Status Indicator: This yellow lamp is lit
whenever the control detects a warning condition.
After the condition is corrected, warning indicators
can be reset by pressing the Reset switch. (It is not
necessary to stop the generator set.)
With the Run/Off/Auto switch in the Auto mode,
warnings can also be reset by cycling the remote re-
set input after the condition is corrected.
Shutdown Status Indicator: This red lamp is lit
whenever the control detects a shutdown condition.
After the condition is corrected, shutdown indica-
tors can be reset by turning the Run/Off/Auto switch
to the Off position, and pressing the Reset switch.
In Auto mode, shutdowns can be reset by removing
the remote start input and then cycling the remote
reset input.
Emergency Stop shutdown status (Code 102) can be
reset only at the PCC front panel.