2-8
Copyright 2017 Cummins Inc.
GEN MENU
The facing page shows a block representation of
the GEN menu. If you press the button next to the
word “GEN” in the display, the first GEN submenu
will appear.
As shown in the diagram, the GEN menu has three
submenus.
VOLTS/AMPS submenu: This is the first subme-
nu. Select VOLTS for a display of a line-line or line-
neutral selection. Select line-line or line-neutral for
the desired voltage display. Select AMPS for a dis-
play of L1, L2, and L3 current in amps. When volt-
age or current parameters are displayed, pressing
the button next to the “<<” will return the display
(“BACK”) to the L-L/L-N submenu.
If DELTA is selected in the Initial Start Setup subme-
nu, when selecting VOLTS, the “line-line” or “line-
neutral” submenus will not be displayed, only the
L1-2, L2-3, L3-1 submenu will be displayed.
POWER / KW HOURS submenu: From the VOLTS/
AMPS submenu, press the button next to the “>>” in
the display to move to the POWER/KW HOURS sub-
menu. Select POWER for a display of power output
in kilowatts and a power factor value. Select KW
HOURS for a display of kilowatt hours. When power
or kW hours parameters are displayed, pressing the
button next to the “<<” will return the display
(“BACK”) to the POWER/KW HOURS submenu.
The PF reading will contain an asterisk if the power
factor is leading (for example, *.3PF).
N/A is displayed in the PF field when the generator
set is not running.
%GOV/REG/FREQUENCY submenu: From the
POWER/KW HOURS submenu, press the button
next to the “>>” in the display to move to the %GOV/
REG/FREQUENCY submenu. Select %GOV/REG
for a display of voltage regulator and governor duty
cycle (drive) levels in percentage of maximum. Se-
lect FREQUENCY for a display of the alternator out-
put frequency. When voltage regulator and gover-
nor or frequency parameters are displayed, press-
ing the button next to the “<<” will return the display
(“BACK”) to the %GOV/REG/FREQUENCY sub-
menu.