Curtis 1298 Manual, OS 11
H
-4 Adjustments (see pages 46 and 51–52)
Test the hydraulic system and adjust the Pump Max PWM and PD Max Current
(if a proportional valve is used) to give the desired performance.
To further tune the Lift response, adjust the Pump Accel Rate and Pump
Decel Rate.
To further tune the Lower response, adjust the Lower Accel Rate and
Lower Decel Rate.
If a bump is felt at the end of Lift or Lower operation, increase the Load
Hold Delay value to allow the hydraulic fluid to stop flowing before the load
hold valve closes.
Set the Lift BDI Lockout and Hyd Inhibit Type (HPD) parameters as
required by the application.
5 — INITIAL SETUP