Loading...
9 | Electrical installation
Installer reference guide
126
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
Item Description
(in case of DHW tank)
Power supply for booster
heater (from indoor unit to
DHW tank)
See:
Installation manual of the DHW tank
Addendum book for optional equipment
Wires: (2+GND)×2.5mm²
[9.4] Booster heater
(in case of DHW tank)
Power supply for booster
heater (from mains to
indoor unit)
See:
Installation manual of the domestic hot
water tank
Addendum book for optional equipment
Wires: 2+GND
Maximum running current: 13A
[9.4] Booster heater
LAN adapter See:
Installation manual of the LAN adapter
Addendum book for optional equipment
Wires: 2×(0.75~1.25mm²). Must be
sheathed.
Maximum length: 200m
See installation manual of the LAN adapter
WLAN cartridge See:
Installation manual of the WLAN cartridge
Installer reference guide
[D] Wireless gateway
WLAN module See:
Installation manual of the WLAN module
Addendum book for optional equipment
Installer reference guide
Use the cable delivered with the WLAN
module.
[D] Wireless gateway
Bizone kit See:
Installation manual of the bizone kit
Addendum book for optional equipment
Use the cable delivered with the bizone kit.
[9.P] Bizone kit