[9] Relay 9
[36] Control word bit 11
[37] Control word bit 12
5-41 On Delay, Relay
Array [8] (Relay 1 [0], Relay 2 [1], Relay 7 [6], Relay 8 [7], Relay 9
[8])
0.01s
*
[0.01 - 600.00 s ] Enter the delay of the relay cut-in time. Select one of available
mechanical relays and MCO 105 in an array function. See par.
5-40.
5-42 Off Delay, Relay
Array [8] (Relay 1 [0], Relay 2 [1], Relay 7 [6], Relay 8 [7], Relay 9
[8])
0.01s
*
[0.01 - 600.00 s.] Enter the delay of the relay cut-out time. Select one of available
mechanical relays and MCO 105 in an array function. See par.
5-40.
If the Selected Event condition changes before the on- or off
delay timer expires, the relay output is unaffected.