EasyManuals Logo

Danfoss TTS700 User Manual

Danfoss TTS700
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #253 background imageLoading...
Page #253 background image
Table 5-3 Compressor Status 2 Faults
Compressor Status 2 Fault Description
SuctionPressureSensorFault
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadablerange
andindicatesanerrorinthereading,orafunctionalproblemwiththesensor.-onlyavailablein4.X
SuctionTemperatureSensor
Fault
DischargePressureSensorFault
DischargeTemperatureSensor
Fault
InverterTemperatureSensor
Fault
CavityTemperatureSensorFault
SoftStartTemperatureSensor
Fault
InvalidBearingCalibrationFault AvalidbearingcalibrationisnotstoredintheEEPROM.
InverterCoolingControlFault ThemeasuredInverterTemperaturehasexceededtheCoolingControlFaultlimitaftertheFaultDelaytimerhas
expired.Ifthetemperaturerisesabovethefaultlimit,thefaultdelaytimerwillbegin,ifthetemperaturefalls
belowthefaultlimit,thetimerwillbereset,thecompressorwillstopifthetimerexpires.
MotorCoolingControlFault ThemeasuredCavityTemperaturehasexceededtheCoolingControlFaultlimitaftertheFaultDelaytimerhas
expired.Ifthetemperaturerisesabovethefaultlimit,thefaultdelaytimerwillbegin,ifthetemperaturefalls
belowthefaultlimit,thetimerwillbereset,thecompressorwillstopifthetimerexpires.
Table 5-4 Motor Fault Types
Motor/System Status Description
MotorSinglePhaseOvercurrent
Fault
Measuredpeakcurrentvalueofanysinglephasetomotor(fromInverter)exceedsthefaultlimit.
DCBusOvervoltageFault ThemeasuredDCbusvoltagehasexceededtheMaximumDCBusVoltagelimit,whileRPMis>0
MotorHighCurrentFault ThemotorcurrenthasexceededMaximumMotorCurrentlimit.
InverterError Inverterreportsagenericerror,orcommunicationtoBMCCislost.
BearingFaultActive IfaBearingStatusFaulttypeispresent,thentheBearingFaultActiveistriggered.Thisisnotanactualfault,only
anindicationthatafaulthasoccurredintheBearingStatussection.
RotorStartingTorqueFault MotorCurrentmaximumhasbeenexceededduringcompressorstart-up.
LowInverterCurrentFault Measuredcurrenttomotor(fromInverter)hasnotreachedtheMinimumPowerlimit.
DCBusUnder/OverVoltage
Fault
At0RPM:ThemeasuredDCBusvoltageismeasuredlowerorhigherthantheDCBusUnderorOverVoltageFault
limits.
24VDCUnder/OverVoltage
Fault
Themeasured24VDCsupplyisoutsidetherangeoftheloworhighlimit.
LowMotorBackEMFFault ThecalculatedmotorbackEMFhasfallenbelowtheminimumBackEMFlimit.
EEPROMChecksumFault Anerror(checksumerror)occursreadingthedatatablefromtheEEPROM.
GeneratorModeActive Atgreaterthan0RPMandDCbusvoltagelow,Generatormodeisenabled,switchingtheInvertertorectifier
functiontomaintaintheDCbusvoltageuntiltheshaftcomestoastopanddelevitates.
SCRRippleVoltageFault TheDCbusvoltagerippleexceedstheSCRVoltageRippleFaultlimit.
SysteminStartupmode Thecompressorinitializationhasnotfinished.Pleasewait.Compressorisresettingafterapowercycle.Thisisa
statusmessage.
M-SV-001-EN Rev. H-1/23/2023 Page 253 of 294

Table of Contents

Other manuals for Danfoss TTS700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss TTS700 and is the answer not in the manual?

Danfoss TTS700 Specifications

General IconGeneral
BrandDanfoss
ModelTTS700
CategoryAir Compressor
LanguageEnglish

Related product manuals