015 Reset on LCP
(RESET BUTTON)
Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows selection/deselection of the re-
set key on the control panel.
Description of choice:
If Disable [0] is selected in this parameter, the [RESET]
key will be inactive.
NB!
Only select Disable [0] if an external reset
signal has been connected via the digital
inputs.
016 Lock for data change
(DATA CHANGE LOCK)
Value:
Not locked (NOT LOCKED) [0]
Locked (LOCKED) [1]
Function:
This parameter allows the control panel to be “locked”,
which means that it is not possible to carry out data
modifications via the control unit.
Description of choice:
If Locked [1] is selected, data modifications in the pa-
rameters cannot be made, although it will still be pos-
sible to carry out data modifications via the bus.
Parameters 007-010 Display readout can be changed
via the control panel.
It is also possible to lock for data modifications in these
parameters by means of a digital input, see parame-
ters 300-307 Digital inputs.
017
Operating state at power up, local con-
trol
(POWER UP ACTION)
Value:
Auto restart (AUTO RESTART) [0]
OFF/Stop (OFF/STOP) [1]
Function:
Setting of the desired operating mode when the mains
voltage is reconnected.
Description of choice:
Auto restart [0] is selected if the frequency converter is
to start up in the same start/stop condition as immedi-
ately before power to the frequency converter is cut off.
OFF/Stop [1] is selected if the frequency converter is
to remain stopped when the mains voltage is connec-
ted, until a start command is active. To restart, activate
the key [HAND START] or [AUTO START]
by using
the control panel.
NB!
If [HAND START] or [AUTO START] can-
not be activated by the keys on the control
panel (see parameter 012/014 Hand/Auto
start on LCP) the motor will not be able to
restart if OFF/Stop [1] is selected. If Hand-
start or Autostart has been programmed
for activation via the digital inputs, the mo-
tor will not be able to restart if OFF/Stop
[1] is selected.
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port