Relay outputs Relay no. 1 2
parameter 323 326
Value:
No function (NO FUNCTION)
[0] [0]
Ready signal (READY) [1] [1]
Standby (STAND BY) [2] [2]
Running (RUNNING) [3] [3]
Running at ref. value (RUNNING AT REFERENCE) [4] [4]
Running, no warning (RUNNING NO WARNING) [5] [5]
Local reference active (DRIVE IN LOCAL REF) [6] [6]
Remote references active (DRIVE IN REMOTE REF.) [7] [7]
Alarm (ALARM) [8] [8]
Alarm or warning (ALARM OR WARNING) [9] [9]
No alarm (NO ALARM) [10] [10]
Current limit (CURRENT LIMIT) [11] [11]
Safety interlock (SAFETY INTERLOCK) [12] [12]
Start command active (START SIGNAL APPLIED) [13] [13]
Reversing (RUNNING IN REVERSE) [14] [14]
Thermal warning (THERMAL WARNING) [15] [15]
Hand mode active (DRIVE IN HAND MODE) [16] [16]
Auto mode active (DRIVE IN AUTO MODE) [17] [17]
Sleep mode (SLEEP MODE) [18] [18]
Output frequency lower than f
LOW
parameter 223 (F OUT < F LOW)
[19] [19]
Output frequency higher than f
HIGH
parameter 224 (F OUT > F HIGH)
[20] [20]
Out of frequency range (FREQ RANGE WARN.) [21] [21]
Output current lower than
LOW
parameter 221 (I OUT < I LOW)
[22] [22]
Output current higher than I
HIGH
parameter 222 (I OUT > I HIGH)
[23] [23]
Out of current range (CURRENT RANGE WARN.) [24] [24]
Out of feedback range (FEEDBACK RANGE WARN.) [25] [25]
Out of reference range (REFERENCE RANGE WARN.) [26] [26]
Relay 123 (RELAY 123) [27] [27]
Mains imbalance (MAINS IMBALANCE) [28] [28]
Control word 11/12 (CONTROL WORD 11/12) [29] [29]
Fire mode active (FIRE MODE ACTIVE) [30] [30]
Fire mode bypass (FIRE MODE BYPASS) [31] [31]
Function:
Description of choice:
See description of [0] - [31] in Analogue/digital outputs.
Control word bit 11/12, relay 1 and relay 2 can be
activated via the serial communication. Bit 11 activates
relay 1 and bit 12 activates relay 2.
If the parameter 556 Bus time interval function be-
comes active, relay 1 and relay 2 will become cut off if
they are activated via the serial communication. See
paragraph Serial communication in the Design Guide.
323 Relay 1, output function
(RELAY1 FUNCTION)
Function:
This output activates a relay switch. Relay switch 01
can be used for indicating status and warnings. The
relay is activated when the conditions for the relevant
data values have been fulfilled.
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
136 MG.61.B5.02 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 6000 HVAC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 HVAC Series and is the answer not in the manual?

Danfoss VLT 6000 HVAC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 HVAC Series
CategoryDC Drives
LanguageEnglish

Related product manuals