506 Reversering
(REVERSING)
Value:
Digital input (DIGITAL INPUT) [0]
Serial communication (SERIAL PORT) [1]
Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See functional description under parameter 503
Coasting.
Description of choice:
The table below shows when the motor is running
clockwise and anti-clockwise when Digital input [0],
Serial communication [1], Logic and [2] or Logic or [3]
has been selected.
Digital input [0] Serial communication [1]
Serial Serial
Kl.19
co
m.
Function Kl.19 co
m.
Function
0 0 Clockwise 0 0 Clockwise
0 1 Clockwise 0 1 Counter-
clock
1 0 Counter-
clock.
1 0 Clockwise
1 1 Counter-
clock.
1 1 Counter-
clock.
Logic and [2] Logic or [3]
Serial Serial
Kl.19
co
m.
Function Kl.19 co
m.
Function
0 0 Clockwise 0 0 Clockwise
0 1 Clockwise 0 1 Counter-
clock.
1 0 Clockwise 1 0 Counter-
clock.
1 1 Counter-
clock.
1 1 Counter-
clock.
507 Selection of Setup
(SELECTING OF SETUP)
508 Selection of preset reference
(SELECTING OF SPEED)
Value:
Digital input (DIGITAL INPUT) [0]
Serial communication (SERIAL PORT) [1]
Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See functional description under parameter 503
Coasting.
Description of choice:
The table below shows the Setup (parameter 002 Ac-
tive Setup) that has been selected via Digital input
[0],Serial communication [1], Logic and [2] or Logic or
[3].
The table also shows the preset reference (parame-
ters 211-214 Preset reference) that has been selected
via Digital input [0], Serial communication [1], Logic
and [2] or Logic or [3].
Digital input [0]
Bus
msb
Bus
lsb
Setup/Pre-
set
msb
Setup/Pre-
set
lsb
Setup no.
Preset ref.
no.
0 0 0 0 1
0
0 0 1 2
0
0 1 0 3
0
0 1 1 4
0 1 0 0 1
0
1 0 1 2
0
1 1 0 3
0
1 1 1 4
1 0 0 0 1
1
0 0 1 2
1
0 1 0 3
1
0 1 1 4
1 1 0 0 1
1
1 0 1 2
1
1 1 0 3
1
1 1 1 4