[Index 1-10] Error Code: 0 - 99
Function:
This parameter makes it possible to see the reason
why a trip (cut-out of the frequency converter) occurs.
10 [1-10] log values are stored.
The lowest log number [1] contains the latest/most re-
cently saved data value; the highest log number [10]
contains the oldest data value.
If there is a trip on the frequency converter, it is pos-
sible to see its cause, the time and possibly the values
for output current or output voltage.
Description of choice:
Stated as an error code in which the number refers to
a table in List of warnings and alarms.
The fault log is
only reset after manual initialization.
(See Manual initialization).
616 Fault log: Time
(F. LOG: TIME)
Value:
[Index 1-10] Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total num-
ber of hours run in connection with the 10 latest trips.
10 [1-10] log values are stored. The lowest log number
[1] contains the latest/most recently saved data value,
while the highest log number [10] contains the oldest
data value.
Description of choice:
The fault log is
only reset after manual initialization.
(See Manual initialization).
617 Fault log: Value
(F. LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
This parameter makes it possible to see the value at
which a trip occurred. The unit of the value depends
on the alarm active in parameter 615 Fault log: Error
code.
Description of choice:
The fault log is
only reset after manual initialization.
(See Manual initialization).
618 Reset of kWh counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Reset to zero of parameter 602 kWh counter.
Description of choice:
If Reset [1] has been selected and when the [OK] key
is pressed, the kWh counter of the frequency converter
is reset. This parameter cannot be selected via the se-
rial port, RS 485.
NB!
When the [OK] key has been activated,
the reset has been carried out.
619 Reset of hours-run counter
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Reset to zero of parameter 601 Hours-run.
Description of choice:
If Reset [1] has been selected and when the [OK] key
is pressed, parameter 601 Hours-run is reset. This pa-
rameter cannot be selected via the serial port, RS 485.
NB!
When the [OK] key has been activated,
the reset has been carried out.
620 Operating mode
(OPERATION MODE)
Value:
Normal function (NORMAL OPERATION) [0]
Function with de-activated inverter
(OPER. W/INVERT.DISAB) [1]
Control card test (CONTROL CARD TEST) [2]
Initialisation (INITIALIZE) [3]