PRESET REF. 2 [6]
PRESET REF. 3 [7]
PRESET REF. 4 [8]
AO42 OFF [9]
AO42 ON [10]
AO45 OFF [11]
AO45 ON [12]
RELAY 1 ON [13]
RELAY 1 OFF [14]
RELAY 2 ON [15]
RELAY 2 OFF [16]
START DRIVE [17]
STOP DRIVE [18]
Function:
An action to be executed is selected here.
Description of choice:
When the time in parameter 784 is passed the action
in the corresponding index is executed. To make the
function safe it is only possible to execute a command
related to parameter 783.
789 RTC startup
(RTC startup)
Value:
Execute on actions (EXEC. ON ACTIONS) [0]
Wait new on action (WAIT NEW ON ACTION) [1]
Function:
Decide how the frequency converter shall respond to
actions after start-up.
Description of choice:
It can be chosen if an action, on startup, shall be exe-
cuted even if the ON time was passed some time ago
[0]. Alternatively choose to wait for the next forth com-
ing ON action before executing [1]. When the RTC is
enabled, it must be defined how this should be done.
VLT
®
6000 HVAC Series
184 MG.61.B5.02 - VLT
®