12.7 Wiring Conguration for RS485
Network Connection
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
-
61
68
69
RS-485
+
130BB685.10
Function Setting
Parameter 8-30
Protocol
FC*
Parameter 8-31
Address
1*
Parameter 8-32
Baud Rate
9600*
*=Default value
Notes/comments:
Select protocol, address, and
baud rate in the parameters.
Table 12.11 Wiring Conguration for RS485 Network Connection
12.8
Wiring Conguration for a Motor
Thermistor
NOTICE!
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
Parameters
130BB686.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Function Setting
Parameter 1-90
Motor Thermal
Protection
[2] Thermistor
trip
Parameter 1-93 T
hermistor Source
[1] analog
input 53
*=Default value
Notes/comments:
If only a warning is wanted, set
parameter 1-90 Motor Thermal
Protection to [1] Thermistor
warning.
Table 12.12 Wiring Conguration for a Motor Thermistor
Application Examples
VLT
®
AQUA Drive FC 202
202 Danfoss A/S © 01/2018 All rights reserved. MG22B222
1212

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals