EasyManuals Logo
Home>Danfoss>DC Drives>vlt FC 102

Danfoss vlt FC 102 Programming Guide

Danfoss vlt FC 102
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #110 background imageLoading...
Page #110 background image
6-17 Terminal 53 Live Zero
Option: Function:
Disables the live zero monitoring,
for example if the analog outputs
are used as part of a decentral I/O
system (that is if these are used to
feed a building management
system with data, and not as part
of any control functions related to
the frequency converter).
[0] Disabled
[1] * Enabled
3.8.3 6-2* Analog Input 2
Parameters for conguring the scaling and limits for analog
input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range: Function:
0.07 V* [ 0 - par. 6-21
V]
Enter the low voltage value. This
analog input scaling value should
correspond to the low reference
feedback value set in
parameter 6-24 Terminal 54 Low Ref./
Feedb. Value.
6-21 Terminal 54 High Voltage
Range: Function:
10 V* [ par. 6-20 -
10 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value.
6-22 Terminal 54 Low Current
Range: Function:
4 mA* [ 0 - par. 6-23
mA]
Enter the low current value. This
reference signal should correspond
to the low reference feedback value
set in parameter 6-24 Terminal 54
Low Ref./Feedb. Value. Set the value
at >2 mA to activate the live zero
timeout function in
parameter 6-01 Live Zero Timeout
Function.
6-23 Terminal 54 High Current
Range: Function:
20 mA* [ par. 6-22 -
20 mA]
Enter the high current value
corresponding to the high reference
feedback value set in
6-23 Terminal 54 High Current
Range: Function:
parameter 6-25 Terminal 54 High
Ref./Feedb. Value.
6-24 Terminal 54 Low Ref./Feedb. Value
Range: Function:
0* [-999999.999
- 999999.999 ]
Enter the analog input scaling value
that corresponds to the low
voltage/low current value set in
parameter 6-20 Terminal 54 Low
Voltage and parameter 6-22 Terminal
54 Low Current.
6-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
100* [-999999.999
- 999999.999 ]
Enter the analog input scaling value
that corresponds to the high
voltage/high current value set in
parameter 6-21 Terminal 54 High
Voltage and parameter 6-23 Terminal
54 High Current.
6-26 Terminal 54 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the lter time constant. This is
a rst-order digital low-pass lter
time constant for suppressing
electrical noise in terminal 54.
Increasing the value improves
dampening but also increases the
time delay through the lter.
6-27 Terminal 54 Live Zero
Option: Function:
Disables the live zero-monitoring,
for example if the analog outputs
are used as part of a decentral I/O
system (that is if these are used to
feed a building management
system with data, and not as part
of any control functions related to
the frequency converter).
[0] Disabled
[1] * Enabled
Parameter Descriptions
VLT
®
HVAC Drive FC 102
108 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals