EasyManua.ls Logo

Danfoss vlt FC 102 - Page 112

Danfoss vlt FC 102
322 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-46 Term. X30/12 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the lter time constant. This
constant is a rst-order digital low-
pass lter time for suppressing
electrical noise in terminal X30/12.
A high value improves dampening
but also increases the delay
through the lter.
6-47 Term. X30/12 Live Zero
Option: Function:
This parameter makes it possible to
disable the live zero-monitoring. For
example, to be used if the analog
outputs are used in a decentral I/O
system (when an analog output
does not full any control function,
but feeds a data storage device).
[0] Disabled
[1] * Enabled
3.8.6 6-5* Analog Output 1
Parameters for conguring the scaling and limits for analog
output 1, that is terminal 42. Analog outputs are current
outputs: 0/4–20 mA. Common terminal (terminal 39) is the
same terminal and has the same electrical potential for
analog common and digital common connection.
Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option: Function:
NOTICE
Values for setting the
minimum reference are found
in open loop
parameter 3-02 Minimum
Reference and for closed loop
parameter 20-13 Minimum
Reference/Feedb.. Values for
maximum reference for open
loop are found in
parameter 3-03 Maximum
Reference and for closed loop
parameter 20-14 Maximum
Reference/Feedb.
This parameter enables the function
of terminal 42 as an analog current
6-50 Terminal 42 Output
Option: Function:
output. Depending on the option
selected, the output is either 0–
20 mA or 4–20 mA. The current
value can be read out in the LCP in
parameter 16-65 Analog Output 42
[mA].
[0] No operation
[52] MCO 0-20mA/
0-10V
[53] MCO 4-20mA
[86] Pressure
Sensor 1
[87] Pressure
Sensor 1 (4-20
mA)
[88] Pressure
Sensor 2
[89] Pressure
Sensor 2 (4-20
mA)
[93] Pressure
Sensor 3
[94] Pressure
Sensor 3 (4-20
mA)
[100] Output freq.
0-100
0–100 Hz, (0–20 mA).
[101] Reference
Min-Max
Minimum reference–Maximum
reference, (0–20 mA).
[102] Feedback
+-200%
-200% to +200% of
parameter 20-14 Maximum
Reference/Feedb., (0–20 mA).
[103] Motor cur. 0-
Imax
0–Inverter maximum current
(parameter 16-37 Inv. Max. Current),
(0-20 mA).
[104] Torque 0-Tlim 0–Torque limit
(parameter 4-16 Torque Limit Motor
Mode), (0–20 mA).
[105] Torque 0-
Tnom
0–Motor rated torque, (0–20 mA).
[106] Power 0-Pnom 0–Motor rated power, (0–20 mA).
[107] Speed 0-
HighLim
0–Speed high limit
(parameter 4-13 Motor Speed High
Limit [RPM] and
parameter 4-14 Motor Speed High
Limit [Hz]), (0–20 mA).
[113] Ext. Closed
Loop 1
0–100%, (0–20 mA).
[114] Ext. Closed
Loop 2
0–100%, (0–20 mA).
[115] Ext. Closed
Loop 3
0–100%, (0–20 mA).
Parameter Descriptions
VLT
®
HVAC Drive FC 102
110 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Related product manuals