8-13 Congurable Status Word STW
This parameter enables conguration of bits 12–15 in the status
word.
Array [16]
Option: Function:
[0] No function
[1] * Prole Default The function corresponds to the
prole default selected in
parameter 8-10 Control Prole.
[2] Alarm 68 Only Only set if alarm 68, Safe Torque O
occurs.
[3] Trip excl
Alarm 68
Set if a trip occurs, unless alarm 68,
Safe Torque O is set to execute the
trip.
[10] T18 DI status The bit indicates the status of
terminal 18.
0 indicates that the terminal is low.
1 indicates that the terminal is
high.
[11] T19 DI status The bit indicates the status of
terminal 19.
0 indicates that the terminal is low.
1 indicates that the terminal is
high.
[12] T27 DI status The bit indicates the status of
terminal 27.
0 indicates that the terminal is low.
1 indicates that the terminal is
high.
[13] T29 DI status The bit indicates the status of
terminal 29.
0 indicates that the terminal is low.
1 indicates that the terminal is
high.
[14] T32 DI status The bit indicates the status of
terminal 32.
0 indicates that the terminal is low.
1 indicates that the terminal is
high.
[15] T33 DI status The bit indicates the status of
terminal 33.
0 indicates that the terminal is low.
1 indicates that the terminal is
high.
[16] T37 DI status The bit indicates the status of
terminal 37.
0 indicates that T37 is low (Safe
Torque O).
1 indicates that T37 is high
(normal).
[17] X30/2 DI
status
8-13 Congurable Status Word STW
This parameter enables conguration of bits 12–15 in the status
word.
Array [16]
Option: Function:
[18] X30/3 DI
status
[19] X30/4 DI
status
[21] Thermal
warning
The thermal warning turns on when
the temperature exceeds the limit
in the motor, frequency converter,
brake resistor, or thermistor.
[30] Brake fault
(IGBT)
Output is logic 1 when the brake
IGBT is short-circuited. Use this
function to protect the frequency
converter if there is a fault on the
brake modules. Use the output/
relay to cut out the main voltage
from the frequency converter.
[40] Out of ref
range
[49] Derate active
[54] Running
[59] On Reference
[60] Comparator 0 See parameter group 13-1*
Comparators. If comparator 0 is
evaluated as true, the output goes
high. Otherwise, it is low.
[61] Comparator 1 See parameter group 13-1*
Comparators. If comparator 1 is
evaluated as true, the output goes
high. Otherwise, it is low.
[62] Comparator 2 See parameter group 13-1*
Comparators. If comparator 2 is
evaluated as true, the output goes
high. Otherwise, it is low.
[63] Comparator 3 See parameter group 13-1*
Comparators. If comparator 3 is
evaluated as true, the output goes
high. Otherwise, it is low.
[64] Comparator 4 See parameter group 13-1*
Comparators. If comparator 4 is
evaluated as true, the output goes
high. Otherwise, it is low.
[65] Comparator 5 See parameter group 13-1*
Comparators. If comparator 5 is
evaluated as true, the output goes
high. Otherwise, it is low.
[70] Logic Rule 0 See parameter group 13-4* Logic
Rules. If logic rule 0 is evaluated as
true, the output goes high.
Otherwise, it is low.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
116 Danfoss A/S © 10/2019 All rights reserved. M0010001