14-61 Function at Inverter Overload
Option: Function:
Is used in case of steady overload
beyond the thermal limits (110% for
60 s).
[0] * Trip Select [0] Trip to make the
frequency converter trip and issue
an alarm.
[1] Derate Reduces pump speed to decrease
the load on the power section and
allowing this to cool down.
14-62 Inv. Overload Derate Current
Range: Function:
95 %* [50 - 100 %] Enter the current level (in % of
rated output current for the
frequency converter) when running
with reduced pump speed after
load on the frequency converter
has exceeded the allowable limit
(110% for 60 s).
14-90 Fault Level
Array [21]. Use this parameter to customize fault levels.
Option: Function:
[0] O Use [0] O with caution as it
ignores all warnings and alarms for
the selected source.
[1] Warning
[2] Trip Changing a fault level from default
option [3] Trip Lock to [2] Trip leads
to the automatic reset of the alarm.
For alarms involving overcurrent,
the frequency converter has a
hardware protection that issues a 3-
minute recovery after 2 consecutive
overcurrent incidents, this hardware
protection cannot be overruled.
[3] Trip lock
[4] Trip w.
delayed reset
This option adds a delay between
automatic resets, otherwise it is the
same as option [2] Trip. The delay
prevents a situation where reset is
attempted repeatedly for an
overcurrent situation. Hardware
protection of the frequency
converter forces the 3-minute
recovery time after 2 consecutive
overcurrents (within a short time
window).
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 155
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals