Parameter
Alarm/
Warning
number
Description [0] O [1] Warning [2] Trip [3] Trip lock
[4] Trip
with
delayed reset
1490.0 1 10 V low D
1490.1 47 24 V low X D
1490.2 48 1.8 V supply low D
1490.3 64 Voltage limit D
1490.4 14 Ground fault during ramping D
1490.5 45
Ground fault 2 during cont.
operation
D
1490.6 12 Torque limit D
1490.7 13 Overcurrent D X
1490.8 16 Short circuit D
1490.9 29 Heat sink temperature D
1490.10 39 Heat sink sensor D
1490.11 65 Control card temperature D
1490.12 69 Power card temperature D
1490.13 244 Heat sink temperature D
1490.14 245 Heat sink sensor D
1490.15 247 Power card temperature D
1490.16 30-32 Motor phase missing D
1490.17 100 Derag limit fault D
1490.18 9 Inverter overloaded X D
1490.19 59 Current limit X D
1490.20 99 Locked rotor X D
Table 3.20 Selection of Choice of Action when Selected Alarm Appears
Parameter Descriptions
VLT
®
HVAC Drive FC 102
156 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals