EasyManuals Logo
Home>Danfoss>DC Drives>vlt FC 102

Danfoss vlt FC 102 Programming Guide

Danfoss vlt FC 102
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #203 background imageLoading...
Page #203 background image
22-23 No-Flow Function
Common actions for low-power detection and low-speed
detection (individual selections not possible).
Option: Function:
[0] * O
NOTICE
Do not set
parameter 14-20 Reset Mode, to
[13] Innite auto reset, when
parameter 22-23 No-Flow
Function is set to [3] Alarm.
Doing so causes the frequency
converter to continuously cycle
between running and stopping
when a no-ow condition is
detected.
NOTICE
Disable the automatic bypass
function of the bypass if the
frequency converter is
equipped with a constant-
speed bypass with an
automatic bypass function
starting the bypass if the
frequency converter
experiences a persistent alarm
condition, and [3] Alarm is
selected as the no-ow
function.
[1] Sleep Mode The frequency converter enters
sleep mode and stops when a no-
ow condition is detected. See
parameter group 22-4* Sleep Mode
for programming options for sleep
mode.
[2] Warning The frequency converter continues
to run, but activates a no-ow
warning (warning 92, NoFlow). A
digital output or a serial communi-
cation bus can communicate a
warning to other equipment.
[3] Alarm The frequency converter stops
running and activates a no-ow
alarm (alarm 92, NoFlow). A
frequency converter digital output
or a serial communication bus can
communicate an alarm to other
equipment.
22-24 No-Flow Delay
Range: Function:
10 s* [1 - 600 s] Set the time that low power/low
speed must stay detected to
22-24 No-Flow Delay
Range: Function:
activate a signal for actions. If
detection disappears before the
timer runs out, the timer is reset.
22-26 Dry Pump Function
Select the action for dry-pump operation.
Option: Function:
[0] * O
[1] Warning
NOTICE
To use dry-pump detection:
1. Enable low-power
detection in
parameter 22-21 Low
Power Detection.
2. Commission low-
power detection
using either
parameter group 22-3*
No-ow Power Tuning
No Flow Power Tuning,
or
parameter 22-20 Low
Power Auto Set-up.
NOTICE
Do not set
parameter 14-20 Reset Mode to
[13] Innite auto reset, when
parameter 22-26 Dry Pump
Function is set to [2] Alarm.
Doing so causes the frequency
converter to continuously cycle
between running and stopping
when a dry-pump condition is
detected.
NOTICE
For frequency converters with
constant-speed bypass.
If an automatic bypass
function starts the bypass at
persistent alarm conditions,
disable the automatic bypass
function, if [2] Alarm or [3]
Man. Reset Alarm is selected as
the dry-pump function.
The frequency converter continues
to run, but activates a dry-pump
warning (warning 93, Dry pump). A
frequency converter digital output
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 201
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals