1-47 Torque Calibration
Option: Function:
Parameter 1-30 Stator
Resistance (Rs).
Parameter 1-33 Stator
Leakage Reactance (X1).
Parameter 1-34 Rotor
Leakage Reactance (X2).
Parameter 1-37 d-axis
Inductance (Ld).
1-48 Inductance Sat. Point
Range: Function:
Size
related*
[1 - 500 %]
NOTICE
Run an AMA to set the value
of this parameter. Edit the
value manually only when the
application requires a value
other than determined by
AMA.
Select the d-axis inductance
saturation point. The frequency
converter uses this value to
optimize the performance of SynRM
motors.
Select the value that matches the
point where the inductance equals
the mean value of
parameter 1-37 d-axis Inductance
(Ld) and parameter 1-44 d-axis
Inductance Sat. (LdSat), as
percentage of nominal current.
1-49 q-axis Inductance Sat. Point
Range: Function:
Size
related*
[ 0 - 200 %]
NOTICE
Run an AMA to set the value
of this parameter. Edit the
value manually only when the
application requires a value
other than determined by
AMA.
Enter the q-Axis inductance
saturation point. The frequency
converter uses this value to
optimize the performance of IPM
motors.
Select the value that matches the
point where the inductance equals
the average value of
parameter 1-38 q-axis Inductance
(Lq) and parameter 1-45 q-axis
1-49 q-axis Inductance Sat. Point
Range: Function:
Inductance Sat. (LqSat), as
percentage of nominal current.
3.3.7 1-5* Load Indep. Setting
1-50 Motor Magnetisation at Zero Speed
This parameter is not visible on the LCP.
Range: Function:
100 %* [0 - 300 %]
NOTICE
Parameter 1-50 Motor Magneti-
sation at Zero Speed has no
eect when
parameter 1-10 Motor
Construction = [1] PM, non-
salient SPM.
Use this parameter along with
parameter 1-51 Min Speed Normal
Magnetising [RPM] to obtain a
dierent thermal load on the motor
when running at low speed.
Enter a value which is a percentage
of the rated magnetizing current. If
the setting is too low, the torque
on the motor shaft may be
reduced.
Magn. current
130BA045.11
Hz
Par.1-50
Par.1-51
100%
Par.1-52 RPM
Illustration 3.8 Motor Magneti-
zation
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 59
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL