EasyManua.ls Logo

Danfoss vlt FC 102 - Page 71

Danfoss vlt FC 102
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-93 Thermistor Source
Option: Function:
or parameter 3-17 Reference 3
Source).
When using VLT
®
PTC Thermistor
Card MCB 112, always select [0]
None.
[0] * None
[1] Analog Input
53
[2] Analog Input
54
[3] Digital input
18
[4] Digital input
19
[5] Digital input
32
[6] Digital input
33
1-94 ATEX ETR cur.lim. speed reduction
Range: Function:
0 %* [0 - 100 %] Only visible if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR.
Congure the reaction for operating in Ex-e current limit.
0%: The frequency converter does not change anything
besides issuing warning 163, ATEX ETR cur.lim.warning.
>0%: The frequency converter issues warning 163, ATEX ETR
cur.lim.warning and reduces motor speed following ramp 2
(parameter group 3-5* Ramp 2).
Example:
Actual reference = 50 RPM
Parameter 1-94 ATEX ETR cur.lim. speed reduction = 20%
Resulting reference = 40 RPM
1-95 Thermistor Sensor Type
Option: Function:
Select the type of the thermistor
sensor.
[0] * KTY Sensor 1
1 kΩ at 100 °C (212 °F).
[1] KTY Sensor 2
1 kΩ at 25 °C (77 °F).
[2] KTY Sensor 3
2 kΩ at 25 °C (77 °F).
[3] Pt1000
1-96 Thermistor Sensor Source
Option: Function:
Select analog input terminal 54 as a
thermistor sensor input. Terminal 54
cannot be selected as thermistor
source if otherwise used as
1-96 Thermistor Sensor Source
Option: Function:
reference (see
parameter 3-15 Reference Resource 1
to parameter 3-17 Reference Resource
3).
NOTICE
Connection of thermistor
sensor between terminals 54
and 55 (GND).
[0] * None
[2] Analog Input
54
1-97 Thermistor Threshold level
Range: Function:
80 °C* [ -40 -
220 °C]
Select the thermistor sensor
threshold level for motor thermal
protection.
1-98 ATEX ETR interpol. points freq.
Range: Function:
Size
related*
[ 0 - 1000.0
Hz]
NOTICE
Valid for only.
Only visible if parameter 1-90 Motor
Thermal Protection is set to [20].
Enter the 4 frequency points [Hz] from the motor
nameplate into this array. Table 3.10 shows the example of
frequency/current points.
NOTICE
All frequency/current limit points from the motor
nameplate or motor datasheet must be programmed.
1 0 0 %
8 0 %
4 0 %
5 Hz 15 Hz 25 Hz 50 Hz
130BB909.10
Illustration 3.16 Example of ATEX ETR Thermal Limitation
Curve
x-axis: f
m
[Hz]
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 69
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Related product manuals