5-26 Terminal X46/13 Digital Input
Option: Function:
[70] Constant ON
Actions
[75] MCO Specic
[78] Reset Maint.
Word
[80] PTC Card 1
[120] Lead Pump
Start
[121] Lead Pump
Alternation
[130] Pump 1
Interlock
[131] Pump 2
Interlock
[132] Pump 3
Interlock
[190] Fire Mode Ref
Bit 0
[191] Fire Mode Ref
Bit 1
[192] Fire Mode Ref
Bit 2
3.7.10 5-3* Digital Outputs
Parameters for conguring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in parameter 5-01 Terminal 27 Mode and set the
I/O function for terminal 29 in parameter 5-02 Terminal 29
Mode. These parameters cannot be adjusted while the
motor is running.
The digital outputs can be programmed
with these functions:
[0] No operation Default for all digital outputs and relay
outputs.
[1] Control ready The control board receives supply voltage.
[2] Drive ready The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3] Drive ready /
remote
control
The frequency converter is ready for
operation and is in Auto On mode.
[4] Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is
given (start/disable). There are no
warnings.
[5] Running The motor is running.
[6] Running / no
warning
The output speed is higher than the speed
set in parameter 1-81 Min Speed for
Function at Stop [RPM]. The motor is
running and there are no warnings.
[8] Run on
reference / no
warning
The motor runs at reference speed.
[9] Alarm An alarm activates the output. There are
no warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque limit The torque limit set in
parameter 4-16 Torque Limit Motor Mode or
parameter 4-13 Motor Speed High Limit
[RPM] has been exceeded.
[12] Out of current
range
The motor current is outside the range set
in parameter 4-18 Current Limit.
[13] Below current,
low
The motor current is lower than set in
parameter 4-50 Warning Current Low.
[14] Above current,
high
The motor current is higher than set in
parameter 4-51 Warning Current High.
[16] Below speed,
low
The output speed is lower than the setting
in parameter 4-52 Warning Speed Low.
[17] Above speed,
high
The output speed is higher than the
setting in parameter 4-53 Warning Speed
High.
[18] Out of
feedback
range
The feedback is outside the range set in
parameter 4-56 Warning Feedback Low and
parameter 4-57 Warning Feedback High.
[19] Below
feedback low
The feedback is below the limit set in
parameter 4-56 Warning Feedback Low.
[20] Above
feedback high
The feedback is above the limit set in
parameter 4-57 Warning Feedback High.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[25] Reverse The motor runs (or is ready to run)
clockwise when there is a logic 0 signal
and counterclockwise when there is a
logic 1 signal. The output changes as soon
as the reversing signal is applied.
[26] Bus OK Active communication (no time-out) via
the serial communication port.
[27] Torque limit
and stop
Use this option to perform a coasting stop
and in torque limit condition. If the
frequency converter has received a stop
signal and is at the torque limit, the signal
is logic 0.
[28] Brake, no
warning
The brake is active and there are no
warnings.
[29] Brake ready,
no fault
The brake is ready for operation and there
are no faults.
[30] Brake fault
(IGBT)
The output is logic 1 when the brake IGBT
is short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
96 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL