Table 30: Run Permissive
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
e30bb684.11
Drive
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[8] Start*
Parameter 5-11 Terminal 19 Digital Input
[52] Run permissive
Parameter 5-12 Terminal 27 Digital Input
[7] External interlock
Parameter 5-40 Function Relay
[167] Start command act.
*=Default value
Notes/comments:
D IN 37 is an option.
6.1.6 Wiring Configuration: Start/Stop
Table 31: Start/Stop Command with Safe Torque Off Option
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
12
13
18
19
20
27
29
32
33
37
e30bb802.12
Drive
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[Start]*
Parameter 5-12 Terminal 27 Digital Input
[0] No operation
Parameter 5-19 Terminal 37 Safe Stop
[1] Safe Stop Alarm
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27 Digital Input is set [0] No operation, a jumper wire to terminal 27 is
not needed.
D IN 37 is an option.
AQ267037536117en-000101 / 130R008354 | Danfoss A/S © 2023.09
Basic I/O Configuration
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL

Related product manuals