4.4.3 Inside Delta Connection (Bypassed)
NOTICE
Models MCD5-0021B to MCD5-0961B are internally bypassed. Models MCD5-0245C to MCD5-1600C require an external
bypass contactor.
Type code Ampere ratings A]
AC-53b
3-30:330
AC-53b
4.20-:340
AC-53b
4.5-30:330
MCD5-0021B 32 26 22
MCD5-0037B 56 47 39
MCD5-0043B 65 56 45
MCD5-0053B 80 69 55
AC-53b
3-30:570
AC-53b
4-20:580
AC-53b
4.5-30:570
MCD5-0068B 102 83 71
MCD5-0084B 126 104 87
MCD5-0089B 134 112 92
MCD5-0105B 158 143 117
MCD5-0131B 197 159 136
MCD5-0141B 212 181 146
MCD5-0195B 293 241 201
MCD5-0215B 323 268 223
MCD5-0245B 368 291 254
MCD5-0245C 383 302 264
MCD5-0331B 497 400 343
MCD5-0360C 540 465 395
MCD5-0380C 570 539 449
MCD5-0396B 594 478 410
MCD5-0428C 645 552 463
MCD5-0469B 704 575 490
MCD5-0525B 787 637 546
MCD5-0595C 930 810 651
MCD5-0619C 975 842 683
MCD5-0632B 948 768 658
MCD5-0790C 1185 1072 869
MCD5-0744B 1116 910 774
MCD5-0826B 1239 1026 857
MCD5-0927C 1395 1244 992
MCD5-0961B 1441 1194 997
MCD5-1200C 1800 1800 1607
MCD5-1410C 2115 1979 1671
MCD5-1600C 2400 2400 2030
Table 4.4 Bypassed Models
Electrical Installation
VLT
®
Soft Starter MCD 500
22 Danfoss A/S © 05/2016 All rights reserved. MG17K602