EasyManua.ls Logo

Danfoss vlt soft starter mcd 500 - Auxiliary Trip Circuit

Danfoss vlt soft starter mcd 500
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTICE
Although Emergency run fullls the functionality requirements of Fire mode, Danfoss does not recommend its use in
situations that require testing and/or compliance with specic standards as it is not certied.
5.11 Auxiliary Trip Circuit
In normal operation, the VLT
®
Soft Starter MCD 500 is controlled via a remote 2-wire signal (terminals 17, 18).
Input A (terminals 11, 16) is connected to an external trip circuit (such as a low-pressure alarm switch for a pumping
system). When the external circuit activates, the soft starter trips and stops the motor.
K1
F
24
VD
22
21
6/T3
2/T1
13
14
4/T2
24
33
34
06
05
08
07
17
18
25
11
16
A6
A5
A4
5/L3
3/L2
15
S3
S1
S2
E
1/L1
+
+
5
6 7
4
2
A
3
1
177HA525.1
1 Control voltage (model dependent) S1 Start/stop contact
2 24 V DC output S2 Reset contact
3 Remote control inputs S3 Auxiliary trip contact
4 Motor thermistor input (PTC only) 13, 14 Relay output A
5 Relay outputs 21, 22, 24 Relay output B
6 3-phase supply 33, 34 Relay output C
7 Motor terminals
Illustration 5.13 Auxiliary Trip Circuit
Parameter settings:
Parameter 3-3 Input A Function.
- Select Input Trip (N/O) - assigns input A to auxiliary trip (N/O) function.
Parameter 3-4 Input A Name.
Product Features
VLT
®
Soft Starter MCD 500
46 Danfoss A/S © 05/2016 All rights reserved. MG17K602
55

Table of Contents