Environmental
Protection
MCD5-0021B to MCD5-0105B IP20 & NEMA, UL Indoor Type 1
MCD5-0131B to MCD5-1600C IP00, UL Indoor Open Type
Operating temperature -10 °C (14 °F) to +60 °C (140 °F), above 40 °C (104 °F) with derating
Storage temperature -25 °C (-13 °F) to +60 °C
Operating altitude (using MCD PC software) 0–1000 m (0–3281 ft), above 1000 m (3281 ft) with derating
Humidity 5–95% relative humidity
Pollution degree Pollution degree 3
Vibration IEC 60068-2-6
Heat dissipation
During start 4.5 W per ampere
During run
MCD5-0021B to MCD5-0053B ≤39 W approximately
MCD5-0068B to MCD5-0105B ≤51 W approximately
MCD5-0131B to MCD5-0215B ≤120 W approximately
MCD5-0245B to MCD5-0469B ≤140 W approximately
MCD5-0525B to MCD5-0961B ≤357 W approximately
MCD5-0245C to MCD5-0927C 4.5 W per ampere approximately
MCD5-1200C to MCD5-1600C 4.5 W per ampere approximately
Certication
C✓ IEC 60947-4-2
UL/C-UL
MCD5-0021B to MCD5-0396B, MCD5-0245C to MCD5-1600C
MCD5-0469B to MCD5-0961B
MCD5-0021B to MCD5-105B
MCD5-0131B to MCD5-1600C
UL 508
1)
UL-listed
UL-recognized
IP20, when tted with optional nger guard kit
CE IEC 60947-4-2
CCC GB 14048-6
Marine
(MCD5-0021B to MCD5-0961B) Lloyds Marine No 1 Specication
RoHS Compliant with EU Directive 2002/95/EC
1) For UL certication extra requirements may apply, depending on the models. For details, see chapter 11.1 UL-compliant Instal-
lation.
11.1
UL-compliant Installation
This section details more requirements and conguration
settings for the VLT
®
Soft Starter MCD 500 to be UL-
compliant. See also Table 4.12.
11.1.1 Models MCD5-0021B to
MCD5-0105B
There are no additional requirements for these models.
11.1.2 Models MCD5-0131B to
MCD5-0215B
•
Use with nger guard kit, ordering number
175G5662.
•
Use the recommended pressure terminal/
connector kit. See Table 11.1 for more
information.
11.1.3 Models MCD5-0245B to
MCD5-0396B
•
Use with nger guard kit, ordering number
175G5730.
•
Use the recommended pressure terminal/
connector kit. See Table 11.1 for more
information.
11.1.4 Models MCD5-0245C
•
Use the recommended pressure terminal/
connector kit. See Table 11.1 for more
information.
Specications Operating Guide
MG17K602 Danfoss A/S © 05/2016 All rights reserved. 83