Figure 72. Installing a PIB
Next steps
1 Install PSUs.
2 Install the MiniPERC riser.
3 Install the cooling fans.
4 Install the air shroud.
5 Follow the procedure listed in After working inside your system.
Control panel
A control panel allows you to manually control the inputs to the server.
Your system supports:
• Left control panel: Contains status LEDs, system ID button, and iDRAC Quick Sync 2 (optional).
• Right control panel: Contains power button, USB 2.0 port, micro USB for iDRAC Direct, and status LED for iDRAC Direct.
Removing the left control panel
Prerequisites
1 Follow the safety guidelines listed in Safety instructions.
2 Follow the procedure listed in Before working inside your system.
NOTE
: Ensure that you note the routing of the cables as you remove them from the system board. You must route the
cables properly when you replace them to prevent the cables from being pinched or crimped.
3 Remove the internal MiniPERC riser.
Installing and removing system components
111