Table 20. Relative humidity specications
Relative humidity Specications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be
non-condensing at all times.
Operating 5% to 85% relative humidity with 29°C (84.2°F) maximum dew point.
Table 21. Maximum vibration specications
Maximum vibration Specications
Operating Random vibration per Mil-Std 810G method 514.6, 0.00220783
g
2
/Hz at 10
Hz to 500 Hz (overall 1.04
rms
), all 3 axes, 1 hour per axis
Storage Mil-Std 810G Procedure I, Cat 4, Fig 514.6C-1 (US highway truck vibration), 1
hour per axes
Table 22. Maximum shock specications
Maximum shock Specications
Operating Mil-Std 810G method 516.6, Proc I, 40G, 11 ms, 3 shocks in +/- directions in 3
axes (total 18 shocks)
Storage Mil-Std 810G method 516.6, Proc I, 40G, 11 ms, 3 shocks in +/- directions in 3
axes (total 18 shocks)
Table 23. Maximum altitude specications
Maximum altitude Specications
Operating Mil-Std 810G method 500.5, Proc. II, air carriage, 15,000 ft for 1 hour after
stabilization
Storage Mil-Std 810G method 500.5, Proc. I, 40,000 ft for 1 hour after stabilization
Particulate and gaseous contamination specications
The following table denes the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specied limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the customer.
Table 24. Particulate contamination
specications
Particulate contamination Specications
Air ltration Data center air ltration as dened by ISO Class 8 per ISO 14644-1 with a
95% upper condence limit.
NOTE: This condition applies to data center environments only. Air
ltration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an oce or
factory oor.