EasyManua.ls Logo

Delta VFD-MS300 - Using Old Delta Standards (Only Speed Mode Is Supported)

Delta VFD-MS300
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VFD-MS300/MH300 EtherNet/IP Communication Card CMM-EIP01
CMM-EIP01 Operation Manual
18
4.2 Using old Delta Standards (only speed mode is supported)
4.2.1 Basic VFD Configurations
In order to operate the drive via Delta-defined control modes, refer to the following
configuration procedure.
1. Wiring (refer to 3.3 EtherNet/IP wiring).
2. Setting source of operation: Drive parameter setting 00-21=5. Selected operational
command comes from EtherNet/IP settings. (Run / stop, forward / reverse rotation, etc.)
3. Setting frequency source: Drive parameter setting 00-20=8. Selected frequency
command comes from EtherNet/IP settings.
4. Selecting control mode by using old Delta definitions: Drive parameter setting 09-30=0.
5. Setting EtherNet/IP format: Drive parameter 09-75 can be used to set up the IP
configuration format (default 0 = static IP; 1 = dynamic IP / DHCP).
6. Setting the IP address of the EtherNet/IP communication card: Drive parameters 09-76,
09-77, 09-78, and 09-79 can be used to configure the IP address (default IP address:
192.168.01.05).
7. Setting EtherNet/IP communication card's netmask: Netmask can be set via drive
parameters 09-80, 09-81, 09-82, and 09-83 (default netmask: 255.255.255.0).
8. Setting the gateway for the EtherNet/IP communication card: Gateway can be configured
via drive parameters 09-84, 09-85, 09-86, and 09-87 (default gateway: 192.168.01.01).
4.2.2 Using Speed Mode as a Control Method
1. Setting the target frequency: Set (Object, Instance, Attribute) = (300h, 20h, 01h),
Unit = Hz, with a decimal precision at the hundredths position. Example: 1000 represents
10.00.
2. Operation: Setting (Object, Instance, Attribute) = (300h, 20h, 00h) = 0002H indicates run,
and (Object, Instance, Attribute) = (300h, 20h, 00h) = 0001H indicates stop.
3. Acceleration/deceleration time operations: If the first acceleration / deceleration section
is used as the basis, the acceleration time is set to (Object, Instance, Attribute) = (300h,
01h, 12h) and the time is set to (Object, Instance, Attribute) = (300h, 01h, 13h) , with unit
= seconds and a decimal precision at the tenths position. Example: 100 represent 10.0
seconds.

Table of Contents

Related product manuals