Chapter 4 Parameters|VFD-VL
4-56
Positive torque
Rever se
03-00~0 2=7
Positive to rque limit
03-00~0 2=8
Negative torque limit
03-00~0 2=9
Reg enerative
torque limit
03-00~0 2=10
Positive/negat ive torque limit
Negative Torque
Forward
03-00~0 2=10
Positive/negative torque limit
03-00~0 2=9
Reg enerative
torque limit
07-19: Source of torque offse
03-00~02: Analog input selections (AUI1/ACI/AUI2)
03-03~05: Analog input bias (AUI1/ACI/AUI2)
03-06~08: AUI1/ACI/AUI2 bias mode
07-19=1
Analog input
03-00~02=3
Bias mode
03-06~08
B ias
03-03~05
+
+/-
Analog input gain
03-09~11
Torque
for preload
03-03
Analog Input Bias 1 (AUI1)
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0.0
Settings -100.0~100.0%
It is used to set the corresponding AUI1 voltage of the external analog input 0.
03-04
Analog Input Bias 1 (ACI)
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0.0
Settings -100.0~100.0%