EasyManua.ls Logo

Delta VFD-VL Series

Delta VFD-VL Series
275 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameters|VFD-VL
4-22
4.2 Description of Parameter Settings
4.2.1 Group 0 User Parameters
: This parameter can be set during operation.
00-00
Identity Code of the AC Motor Drive
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: ##
Settings Read Only
00-01
Rated Current Display of the AC Motor Drive
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: ##
Settings Read Only
Pr. 00-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
Pr.00-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
230V Series
kW 5.5 7.5 11 15 18.5 22 30 37
HP 7.5 10 15 20 25 30 40 50
Pr.00-00 12 14 16 18 20 22 24 26
Rated Output Current for General
Purposes (A)
21.9 27.1 41 53 70 79 120 146
Rated Output Current for Elevators (A) 25 31 47 60 80 90 150 183
Max. Carrier Frequency 15kHz 9kHz
460V Series
kW 5.5 7.5 11 15 18.5 22 30 37 45 55 75
HP 7.5 10 15 20 25 30 40 50 60 75 100
Pr.00-00 13 15 17 19 21 23 25 27 29 31 33
Rated Output Current for General
Purposes (A)
12.3 15.8 21 27 34 41 60 73 91 110 150
Rated Output Current for Elevators (A) 14 18 24 31 39 47 75 91 113 138 188
Max. Carrier Frequency 15kHz 9kHz 6kHz
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com

Table of Contents

Related product manuals