Chapter 4 Parameters|VFD-VL
4-64
05-06
Rs of Motor
Control
mode
SVC FOCPG TQCPG
Factory setting: 0.000
05-07
Rr of Motor
Control
mode
SVC FOCPG TQCPG
Factory setting: 0.000
Settings
0.000~65.535Ω
05-08
Lm of Motor
Control
mode
SVC FOCPG TQCPG
Factory setting: 0.0
05-09
Lx of Motor
Control
mode
SVC FOCPG TQCPG
Factory setting: 0.0
Settings 0.0~6553.5mH
05-10
Torque Compensation Time Constant
Control
mode
SVC
Factory setting: 0.020
Settings 0.001 to 10.000 sec
05-11
Slip Compensation Time Constant
Control
mode
SVC
Factory setting: 0.100
Settings 0.001 to 10.000 sec
Setting Pr.05-10 and Pr.05-11 change the response time for the compensation.
When Pr.05-10 and Pr.05-11 are set to 10 seconds, its response time for the compensation
will be the longest. But if the settings are too short, unstable system may occur.
05-12
Torque Compensation Gain
Control
mode
VF VFPG
Factory setting: 0
Settings 0 to10
This parameter may be set so that the AC motor drive will increase its voltage output to obtain
a higher torque.
05-13
Slip Compensation Gain
Control
mode
SVC VFPG SVC
Factory setting: 0.00
Settings 0.00 to10.00
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-VL Series and is the answer not in the manual?

Delta VFD-VL Series Specifications

General IconGeneral
BrandDelta
ModelVFD-VL Series
CategoryDC Drives
LanguageEnglish

Related product manuals