Chapter 4 Parameters|VFD-VL
4-105
Exception
code
Explanation
03
Illegal data value:
The data value received in the command message is not available
for the AC drive.
04
Slave device failure:
The AC motor drive is unable to perform the requested action.
10
Communication time-out:
If Pr.09-03 is not equal to 0.0, Pr.09-02=0~1, and there is no
communication on the bus during the Time Out detection period (set
by Pr.09-03), “cE10” will be shown on the keypad.
09-05
Response Delay Time
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory Setting: 2.0
Settings 0.0 ~ 200.0 ms
This parameter is the response delay time after AC drive receives communication command
as shown in the following.
PC or PLC command
Handling time
of the AC drive
Response Delay Time
Response Message
of the AC Drive
RS-485 BUS