Chapter 4 Parameters|VFD-VL
4-3
Pr.
Explanation Settings
Factory
Setting
VF
VFPG
SVC
FOCPG
TQCPG
FOCPM
4: Torque control + Encoder (TQCPG)
8: FOC PM control (FOCPM)
00-10
Speed Unit
0: Hz
1: m/s
2: ft/s
0
○ ○ ○ ○ ○ ○
00-11
Output Direction Selection
0: FWD: counterclockwise, REV: clockwise
1: FWD: clockwise, REV: counterclockwise
0
○ ○ ○ ○ ○ ○
00-12
Carrier Frequency
2~15KHz 12
○ ○ ○ ○ ○ ○
00-13
Auto Voltage Regulation
(AVR) Function
0: Enable AVR
1: Disable AVR
2: Disable AVR when deceleration stop
0
○ ○ ○ ○ ○ ○
00-14
Source of the Master
Frequency Command
1: RS-485 serial communication or digital keypad (KPVL-CC01)
2: External analog input (Pr. 03-00)
3: Digital terminals input (Pr. 04-00~04-15)
1
○ ○ ○ ○ ○
00-15
Source of the Operation
Command
1: External terminals
2: RS-485 serial communication or digital keypad (KPVL-CC01)
1
○ ○ ○ ○ ○ ○