CT100 inverter Detailed instructions of function parameters
137
F12.01
Baud rate
Setting range: 05
Default
value: 4
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
5: 38400bps
F12.02
Data check
Setting range: 05
Default
value: 1
Define the data format for Modbus:
0: no check (N, 8,1) for RTU
1: even check (E, 8,1) for RTU
2: odd check (O, 8,1) for RTU
3: no check (N, 8,2) for RTU
4: even check (E, 8,2) for RTU
5: odd check (O, 8,2) for RTU
F12.02
Data format
Data bit
Check
method
Stop bit
0
RTU
8
No check N
1
1
RTU
8
Even check E
1
2
RTU
8
Odd check O
1
3
RTU
8
No check N
2
4
RTU
8
Even check E
2
5
RTU
8
Odd check O
2
Table 6-4 Modbus data format