CT100 inverter Detailed instructions of function parameters
104
output frequency will drop, when the inverter output frequency reaches the lower
limit frequency, the inverter keep running at the lower limit frequency.
(15: corresponds to 200% of the inverter rated current).
F04.11
Keypad torque
Setting range: -200.0%
200.0%
Default
value: 50.0%
F04.11 is relative to the rated current of the inverter.
F04.12
Upper limit frequency
setting
Setting range: 05
Default
value: 0
0: keypad (F00.07)
1: AI1
2: AI2
3: Pulse input HDI
4: multi-step speed
5: 485 communication
(15: 100% corresponds to the Max. frequency)
F04.13
Min. excitation current
(reserved)
Setting range: 0.050.0%
Default
value: 10.0%
When the motor speed is running above the rated speed, in order to maintain the
output voltage stable, reduce the excitation current, the motor will enter the field
weakening operation. When the motor is weakened, the minimum excitation
current is 100.0% corresponding to F01.11 (motor no load current).
6.6 HMI interface (F05 group)
F05.00
Chinese and English
language
Setting range: 01
Default
value: 0
0: Chinese
1: English (reserved)
F05.01
Parameter initialization
Setting range: 02
Default
value: 0
0: no actuation
1: restore default value.
2: clear the fault record.