CT100 inverter Daily maintenance
150
8.3 Replacement of wear parts
The inverter fan and electrolytic capacitor are easy to be damaged. In order to
ensure the inverter runs safely without faults for a long term, you need to replace
the wear parts periodically. The replacement time for wear parts is as follows:
Fan: it needs to be replaced after using more than 20,000 hours
Electrolytic capacitor: it needs to be replaced after using 30,000 to 40,000
hours
8.4 Storage of the inverter
The storage environment should meet the following conditions:
Table 8-3 Storage environment
Category
Storage environment
Temperature
-40℃~70
Humidity
5%95%, no condensation
Surroundings
No direct sunlight, dust, corrosive gases or vibration (can be
sealed with plastic bags and desiccant)
Note: Long-term storage may cause electrolytic capacitor degradation. The
electrolytic capacitor should be energized once in 2 years and the rated voltage
should rise slowly by the regulator.