CT100 inverter Detailed instructions of function parameters
87
6 Detailed instructions of
function parameters
6.1 Basic function (F00 group)
F00.00
Motor control mode
Setting range: 02
Default value: 0
0: V/F control
It is suitable in cases with low speed control precision and where one inverter
drives multi-motors, such as fans and water pumps.
1: speed sensorless vector control
It is suitable in cases with general speed control precision, low-frequency
large-torque and where one inverter drives several same motors, such as
machine tools, centrifuges, electric locomotives, injection molding machines,
hoisters etc.
2: torque control
It is suitable in cases with high speed control precision, fast dynamic response
and torque control, such as drawing machines, printing and dyeing machinery
etc.
F00.01
Run command channel
Setting range: 02
Default value: 0
Select the control command channel for the inverter.
The control commands include: start, stop, forward running, reverse running,
jogging etc.
0: keypad run command channel (LED off)
Press the RUN, STOP/RESET or MF keys on the keypad to control the inverter
run, stop, forward running, reverse running or jogging.
1: terminal running command channel (LED flickering)
Define the multi-function input terminals DI1 DI7 or HDI to forward running,
reverse running and jogging for inverter operation control. Refer to F06.01
F06.08.
2: 485 run command channel (LED on)
The start and stop of the inverter is controlled by the upper computer through
Modbus.