CT100 inverter Detailed instructions of function parameters
138
Set the delay time when the inverter responses it after receiving the data of the
master.
Communication
timeout detection time
Setting range: 0 .0s , 0.1 ~
100.0s
When the function code is set to 0.0s, the communication timeout fault is invalid.
When the function code is non-zero, if the response of the serial communication
is not received within the set time, the inverter reports E.485 fault.
Communication
timeout error handling
0: alarm and coast to stop
1: no alarm and continue running
2: no alarm and stop according to stop mode (communication mode is valid)
3: no alarm and stop according to stop mode (all control modes are valid)
Communication
processing actuation
selection
LED ones
0: write with response
1: write without response
LED tens
0: set value unsaved after power off
1: set value saved after power off
6.14 Auxiliary functions (F13 group)
Setting range: 0.00 ~
F00.06