CT100 inverter Detailed instructions of function parameters
138
F12.03
Response delay
Setting range: 0200ms
Default
value: 5ms
Set the delay time when the inverter responses it after receiving the data of the
master.
F12.04
Communication
timeout detection time
Setting range: 0 .0s , 0.1
100.0s
Default
value: 0.0
When the function code is set to 0.0s, the communication timeout fault is invalid.
When the function code is non-zero, if the response of the serial communication
is not received within the set time, the inverter reports E.485 fault.
F12.05
Communication
timeout error handling
Setting range: 03
Default
value: 1
0: alarm and coast to stop
1: no alarm and continue running
2: no alarm and stop according to stop mode (communication mode is valid)
3: no alarm and stop according to stop mode (all control modes are valid)
F12.06
Communication
processing actuation
selection
Setting range: 00x11
Default
value: 0x00
LED ones
0: write with response
1: write without response
LED tens
0: set value unsaved after power off
1: set value saved after power off
6.14 Auxiliary functions (F13 group)
F13.00
Jogging frequency
Setting range: 0.00
F00.06
Default value:
5.00Hz
F13.01
Jogging running ACC
Setting range: 0.0
Default value: